Description
The Det-Tronics family of catalytic combustible gas sensors provide unmatched flammable gas detection performance in harsh environments and challenging conditions. The heart of the catalytic sensor consists of a pair of computer matched pellistors (beads) that provide identical electrical resistance in clean air. When flammable gas is present, the active bead catalyzes the combustible gas molecules, while the inactive (reference) bead balances the reaction and compensates for normal changes in the ambient environment. The sophisticated design and construction of Det-Tronics catalytic sensors provides excellent sensitivity, response time, and resistance to physical shock and vibration. All Det-Tronics catalytic gas sensors are poison-resistant, and are constructed with a one-piece 316 stainless steel housing. Other features include an integral thermal barrier to prevent bead interaction, and a sinter bonding technique to ensure superior protection against electromagnetic interference. All sensors are provided with a laser etched identification and approvals label that will withstand exposure to harsh outdoor industrial environments. The CGS can be used for detection of virtually all combustible and flammable gases, including hydrogen, and is compatible with the FlexVu® UD10, Infiniti® U9500, Model 505 transmitter, EQ22xxDCUEX, and STB.Features
One piece design with integral thermal barrier
Sinter bonded flame arrestor provides superior EMI protection
316 stainless steel housing
Excellent impact and vibration resistance
Standard poison-resistant performance rating
FM/CSA/ATEX/IECEx/Brazilian Approvals
Compatible with all Det-Tronics combustible gas transmitters and controllers
Sensor Separation Termination Box (STB) options available
Extended operating temperature range
Comprehensive list of conversion K factors for proper calibration available
3/4 inch NPT or 20 mm thread types
Six inch or optional 30 inch wire lead lengths
Constant voltage or constant current sensor types available.
Specifications
Temperature Range
Operating: –67°F to +257°F (–55°C to +125°C).
Performance: –40°F to +167°F (–40°C to +75°C).
Humidity Range
0 to 99% RH, non-condensing.
Response Time
50% full scale in < 10 seconds with 100% LFL applied.
90% full scale in < 30 seconds with 100% LFL applied.
60% full scale in < 10 seconds with 100% methane by volume in air (CSA flooding test).
Recovery Time
< 30 seconds after exposure to pure methane.
Accuracy / Linearity
±3% LFL from 0 to 50% LFL,
±5% LFL from 51% to 100% LFL.
Long Term Stability
Zero: < 1% LFL per month.
Span: < 1% LFL per month in clean air.
Temperature Stability
< ±5% LFL: –13°F to +167°F (–25°C to +75°C).
< ±10% LFL: –40°F to –13°F (–40°C to –25°C).
Sensor Life
3 to 5 years, when environment is free of substances and conditions known to be detrimental to catalytic sensing elements.
Storage Life
Indefinite, when stored in unopened original packaging.
Calibration Cycle
30 days after initial calibration and every 90 days thereafter, or as required by the application and environment.